首页  科学研究  学术论文  2004年
 
Xie QY, Yuan HY, Guo HL (2004) Journal of Fire Sciences 22(4), 325-337.
文章来源:WOS    作者:SKLFS    发布时间:2011-08-16

Xie QY, Yuan HY, Guo HL (2004) Experimental analysis on false alarms of fire detectors by cooking fumes. Journal of Fire Sciences 22(4), 325-337. [In English]

Web link: http://dx.doi.org/10.1177/0734904104041991

Keywords:

fire detector; false alarms; cooking fumes;

Abstract: Experiments were conducted to analyze the response of ionization and photoelectric detectors to the two typical Chinese cooking fumes simulated in the FE/DE. Four real fire smokes were, also carried out for comparison with the nuisance cooking fumes. The outputs of the ionization and photoelectric detector, CO, CO2 and humidity were recorded throughout the six experiments and were compared. The results of these experiments show that the smoke detectors, especially the ionization detector, are sensitive to cooking fumes and nuisance alarms are easy to happen. It is also indicated that CO and CO2 concentration in the cooking fumes varied much less than those in the four real fire sources. The feasibility of reducing false alarms in kitchen through the use of multi-criteria algorithm, which combines the CO or CO2 with smoke, is discussed as well.

 
 
相关链接
Xie QY, Yuan HY, Guo HL (2004) Journal of Fire Sciences 22(4), 325-337.
联系我们
安徽省合肥市金寨路96号
图书馆VIP
火灾科学国家重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.tsg211.com
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号